Oil/gas Fired Steam Boiler

Detail

 Product introduction of oil/gas fired steam boiler:
Oil/gas Fired Steam Boiler is pan-shell type horizontal three-return fuel oil (gas) boiler developed by absorbing domestic, foreign advanced technology and experience. It runs automatically. After the burner atomizes fuel, the produced torch is full of the wave-type boiler inner and transfers radiation heat through inner wall. This is the first return. The high-temperature smoke gas produced during burning accumulates in burning room and turns to the second return (screw smoke pipe bundle area).After conversion heat change, smoke gas's temperature reduces gradually and then it goes into the front smoke case; And turns into the third return (light pipe bundle area); Finally, it flows into chimney through rear smoke case.

The characters of Oil/gas Fired Steam Boiler
1,This gas/oil fired steam boiler can improve boiler's efficiency, save fuel, reduce cost greatly to reach the aim of high-performance, oil (gas)-saving, safe boiler.
2,The steam boiler has more humanized, safer automatic intelligent control system. It has the advantages of high efficiency, saving energy, environmental protection, easy maintenance, wear resistance and so on.
3,It runs automatically. Burning, water level, temperature and steam pressure are adjusted and protected automatically.
4,The international first-class burner guarantees thermal efficiency and improves integral quality.

Technical Data

The Technical Parameter of Oil/gas Fired Steam Boiler

Model Item

WNS1-1.0
-Y(Q)

WNS2-1.25
-Y(Q)

WNS3-1.25
-Y(Q)

WNS4-1.25
-Y(Q)

WNS6-1.25
-Y(Q)

WNS8-1.25
-Y(Q)

WNS10-1.25
-Y(Q)

WNS15-1.25
-Y(Q)

WNS20-1.25
-Y(Q)

Rated evaporation capacity

t/h

1

2

3

4

6

8

10

15

20

Rated steam

Mpa

1

1.25

1.25

1.25

1.25

1.25

1.25

1.25

1.25

Rated steam temperature

184

194

194

194

194

194

194

194

194

Feed water temperature

20

Designed heat efficiency

%

86

86

88.1

87

89

89

89

91

91

Primary steam valve seat

mm

DN65

DN65

DN80

DN100

DN150

DN150

DN150

DN200

DN200

Diameter of feed water pipe

mm

DN25

DN40

DN40

DN40

DN50

DN50

DN50

DN65

DN80

Power distribution

KW

1.11

2.2

7.5

7.5

12

37

37

45

55

Fuel
consumption

Naphtha

kg/h

73

145

198

270

392

535

700

989

1318

Heavy oil

kg/h

76

157

220

304

425

570

744

1002

1336

Town gas

Nm3/h

170

350

496

675

1006

1266

1654

2288

3050

Natural gas

Nm3/h

85

169

251

334

385

633

827

1043

1390

Dimensions
for shipment

length

mm

3500

4000

4800

4900

7150

7950

8900

9300

9600

width

mm

1900

2450

2500

2500

3300

3300

3370

3300

3800

Height

mm

1900

2500

2600

2700

4000

4100

4300

4500

4800

Maximum weight for shipment

t/h

3.9

6.7

8.5

10

15

21

22.3

32.6

37.8



Inquiry